AVAILABLE TEST METHODS
1. DC HI-POT TEST
Recommended as suitable test method for LV cables (SANS 10198-13:2015 Ed 2).
Has since been removed as a recommended test method in SANS 10198-13:2015
Ed 2)
Advantages:
– Relatively simple and inexpensive test equipment
– Other tests methods are recommended for aged MV XLPE cables with even
testing on PILC cables being contested these days
Disadvantages:
– Unable to detect certain defects
– May lead to space charge accumulation, especially at accessory-to-cable
interface.
– May adversely affect future performance of water-tree-affected XLPE cables